Source: IEE Wiring Regulation (16th Edition) Table 4D1B
Source: IEE Wiring Regulation (16th Edition) Table 4D1B
Source: IEE Wiring Regulation (16th Edition)
This sizing of protective conductor is apply upon phase conductor size in (mm²)
Phase Conductor | Protective conductor (E) | Example ____________
<16.0 mm² Same or 1:1 When RYBN is 10.0 mm² then E shall be 10 mm²
16 ~ 35 mm² Fixed 16mm² When RYBN is 30.0 mm² then E shall be 16 mm²
> 35.0 mm² 1/2 size When RYBN is 75.0 mm² then E shall be 35 mm²
__________________________________________________________________________________